Technical data
Input data
AC operation
|
Nominal input voltage range |
2x / 3x 400 V AC … 500 V AC |
|
Input voltage range |
3x 320 V AC … 575 V AC |
|
Input voltage range AC |
3x 320 V AC … 575 V AC |
|
2x 360 V AC … 575 V AC (for 2-phase operation) |
|
|
Voltage type of supply voltage |
AC |
|
Inrush current |
< 15 A |
|
Inrush current integral (I2t) |
0.2 A2s |
|
AC frequency range |
45 Hz … 65 Hz |
|
Mains buffering time |
> 20 ms (3x 400 V AC) |
|
Current consumption |
3x 0.6 A (400 V AC) |
|
3x 0.5 A (480 V AC) |
|
|
Nominal power consumption |
284.4 VA |
|
Protective circuit |
Transient surge protection; Varistor |
|
Power factor (cos phi) |
0.59 |
|
Typical response time |
< 1 s |
|
Permissible backup fuse |
B6 B10 B16 |
|
Recommended breaker for input protection |
6 A … 16 A |
|
Discharge current to PE |
< 3.5 mA |
Output data
|
Efficiency |
88.5 % (at 400 V AC and nominal values) |
|
Output characteristic |
U/I |
|
Nominal output voltage |
24 V DC ±1 % |
|
Setting range of the output voltage (USet) |
22.5 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted) |
|
Nominal output current (IN) |
10 A (UOUT= 24 V DC) |
|
Derating |
55 °C … 70 °C (2.5 %/K) |
|
Feedback voltage resistance |
35 V DC |
|
Protection against overvoltage at the output (OVP) |
< 35 V DC |
|
Max. capacitive load |
unlimited |
|
Active current limitation |
approx. 15 A |
|
Control deviation |
< 1 % (change in load, static 10 % … 90 %) |
|
< 2 % (change in load, dynamic 10 % … 90 %) |
|
|
< 0.1 % (change in input voltage ±10 %) |
|
|
Residual ripple |
< 10 mVPP |
|
Short-circuit-proof |
yes |
|
Output power |
240 W |
|
Peak switching voltages nominal load |
< 30 mVPP |
|
Maximum no-load power dissipation |
7.5 W |
|
Power loss nominal load max. |
34 W |
|
Rise time |
< 2 ms (UOUT(10 % … 90 %)) |
|
Connection in parallel |
yes, for redundancy and increased capacity |
|
Connection in series |
yes |
Connection data
Input
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.2 mm² |
|
Conductor cross section, rigid max. |
2.5 mm² |
|
Conductor cross section flexible min. |
0.2 mm² |
|
Conductor cross section flexible max. |
2.5 mm² |
|
Conductor cross section AWG min. |
24 |
|
Conductor cross section AWG max. |
14 |
|
Stripping length |
9 mm |
|
Screw thread |
M2,5 |
|
Tightening torque, min |
0.4 Nm |
|
Tightening torque max |
0.5 Nm |
Output
|
Connection method |
Screw connection |
|
Conductor cross section, rigid min. |
0.2 mm² |
|
Conductor cross section, rigid max. |
2.5 mm² |
|
Conductor cross section flexible min. |
0.2 mm² |
|
Conductor cross section flexible max. |
2.5 mm² |
|
Conductor cross section AWG min. |
16 |
|
Conductor cross section AWG max. |
12 |
|
Stripping length |
9 mm |
|
Screw thread |
M2,5 |
|
Tightening torque, min |
0.4 Nm |
|
Tightening torque max |
0.5 Nm |
Signaling
|
Types of signaling |
LED |
|
Operating voltage display |
Green LED |
Signal output
|
Status display |
"DC OK" LED green |
|
Note on status display |
UOUT> 21.5 V: LED lights up |
Electrical properties
|
Number of phases |
3 |
|
Insulation voltage input/output |
3 kV AC (type test) |
|
1.5 kV AC (routine test) |
|
|
Insulation voltage output / PE |
500 V DC |
Product properties
|
Product type |
Power supply |
|
Product family |
ESSENTIAL POWER |
|
MTBF (IEC 61709, SN 29500) |
> 700000 h |
Insulation characteristics
|
Protection class |
I (with PE connection) |
|
Overvoltage category |
III |
|
Degree of pollution |
2 |
Dimensions
|
Dimensional drawing |
![]() |
|
Width |
60 mm |
|
Height |
130 mm |
|
Depth |
152.5 mm |
Installation dimensions
|
Installation distance right/left |
0 mm / 0 mm |
|
Installation distance top/bottom |
50 mm / 50 mm |
Mounting
|
Mounting type |
DIN rail mounting |
|
With protective coating |
no |
Material specifications
|
Housing material |
Metal |
Environmental and real-life conditions
Ambient conditions
|
Degree of protection |
IP20 |
|
Ambient temperature (operation) |
-25 °C … 70 °C (> 55 °C Derating: 2.5 %/K) |
|
Ambient temperature (storage/transport) |
-40 °C … 85 °C |
|
Climatic class |
3K3 (in acc. with EN 60721) |
|
Max. permissible relative humidity (operation) |
≤ 95 % (at 25 °C, non-condensing) |
|
Shock |
18 ms, 30g, in each space direction (according to IEC 60068-2-27) |
|
Vibration (operation) |
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) |
|
15 Hz … 150 Hz, 2.3g, 90 min. |
Standards and regulations
|
Standard – Electrical safety |
EN 60950-1 |
|
Standard – Safety extra-low voltage |
EN 60950-1 (SELV) |
|
Approval – requirement of the semiconductor industry with regard to mains voltage dips |
SEMI F47 – 0706 (200 V AC) |
Approvals
|
CSA |
CSA-C22.2 Nr. 107.1-01 |
|
CSA-C22.2 Nr. 60950-01 |
|
|
UL approvals |
UL/C-UL listed UL 508 |
Conformity/Approvals
|
SIL in accordance with IEC 61508 |
0 |
|
Performance level according to ISO 13849 |
without |
EMC data
|
Electromagnetic compatibility |
Conformance with EMC Directive 2014/30/EU |
|
Low Voltage Directive |
Conformance with Low Voltage Directive 2014/35/EC |
|
EMC requirements for noise emission |
EN 61000-6-3 |
|
EN 61000-6-4 |
|
|
EMC requirements for noise immunity |
EN 61000-6-1 |
|
EN 61000-6-2 |
Noise emission
|
Standards/regulations |
EN 55011 (EN 55022) Class B |
Electrostatic discharge
|
Standards/regulations |
EN 61000-4-2 |
Electrostatic discharge
|
Contact discharge |
8 kV (Test Level 4) |
|
Discharge in air |
8 kV (Test Level 3) |
|
Comments |
Criterion A |
Electromagnetic HF field
|
Standards/regulations |
EN 61000-4-3 |
Electromagnetic HF field
|
Frequency range |
80 MHz … 1 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
1 GHz … 2 GHz |
|
Test field strength |
10 V/m |
|
Frequency range |
2 GHz … 3 GHz |
|
Test field strength |
10 V/m |
|
Comments |
Criterion A |
Fast transients (burst)
|
Standards/regulations |
EN 61000-4-4 |
Fast transients (burst)
|
Input |
4 kV (Test Level 4 – asymmetrical) |
|
Output |
4 kV (Test Level 4 – asymmetrical) |
|
Signal |
2 kV (Test Level 3 – asymmetrical) |
|
Comments |
Criterion A |
Surge voltage load (surge)
|
Standards/regulations |
EN 61000-4-5 |
Surge voltage load (surge)
|
Input |
2 kV (Test Level 3 – symmetrical) |
|
4 kV (Test Level 4 – asymmetrical) |
|
|
Output |
1 kV (Test Level 2 – symmetrical) |
|
2 kV (Test Level 3 – asymmetrical) |
|
|
Comments |
Criterion A |
Conducted interference
|
Standards/regulations |
EN 61000-4-6 |
Conducted interference
|
Frequency range |
0.15 MHz … 80 MHz |
|
Comments |
Criterion A |
|
Voltage |
10 V (Test Level 3) |
Voltage dips
|
Standards/regulations |
EN 61000-4-11 |
Emitted interference
|
Standards/regulations |
EN 61000-6-3 |
|
Radio interference voltage in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
|
Emitted radio interference in acc. with EN 55011 |
EN 55011 (EN 55022) Class B, area of application: Industry and residential |
Criteria
|
Criterion A |
Normal operating behavior within the specified limits. |
|
Criterion B |
Temporary impairment to operational behavior that is corrected by the device itself. |
Commercial data
|
Item number |
1018291 |
|
Packing unit |
1 pc |
|
Minimum order quantity |
1 pc |
|
Sales key |
CMP |
|
Product key |
CMB333 |
|
GTIN |
4055626502632 |
|
Weight per piece (including packing) |
1,500 g |
|
Weight per piece (excluding packing) |
1,464 g |
|
Customs tariff number |
85044095 |
|
Country of origin |
CN |
Related products
-
Quick View
Morbi pulvinar augue lorem
$78.00Original price was: $78.00.$49.00Current price is: $49.00.Add to cartPhasellus massa felis, condimentum quis tortor mattis, condimentum varius eros. Vestibulum quis augue sem. Curabitur non vehicula elit, et cursus tortor. Quisque placerat velit nec nulla sodales, porttitor mattis tortor porta. Praesent gravida leo nibh, vel semper nulla lobortis vel. Donec nisl velit, iaculis ac dolor eget, blandit elementum urna.
-
Quick View
Fusce nec diam et dolor
$45.00Add to cartFusce nec diam et dolor ornare rhoncus nec ut mauris. In eleifend mi in felis dictum fermentum. Morbi vel arcu sit amet dolor venenatis bibendum in eu dui. Nulla velit dolor, imperdiet consectetur luctus ut, faucibus eget est.
-
Quick View
Donec ullamcorper turpis
$45.00Add to cartAliquam porttitor mattis erat, a eleifend lorem tempor ut. Donec erat lacus, ultricies at dolor sed, accumsan sollicitudin libero. Praesent pellentesque sed odio et fringilla. Donec a semper metus. Nulla mollis sodales sem vitae congue. Donec laoreet nunc sed metus pretium volutpat. Nunc quis feugiat elit.
-
Quick View
Vestibulum ante ipsum primis
$56.00Add to cartCras mollis dolor sed tempor iaculis. Duis ac ante quam. Donec nec justo erat. Nam a augue vel ex venenatis interdum sit amet ac quam. Interdum et malesuada fames ac ante ipsum primis in faucibus. Vestibulum erat lectus, cursus at dui in, fringilla commodo lectus. Quisque eu bibendum quam, eget euismod sem






Reviews
There are no reviews yet.